BESS sizing calculator for industry

Size a GeoLithium battery energy storage system from your machines, then design it: live single-line diagram, container, bill of materials and cost, with solar, grid and DG options.

List the machines the battery must run. Starting method decides the inrush: DOL motors draw about 6× their running current, star-delta about 2.5×, soft starters about 3×, VFD drives about 1.2×. Load factor is how hard the machine runs on average.

3D illustration: containerised battery energy storage system (BESS)
3D illustration: industrial plant with rooftop solar and machinery

Step 2

Design your GeoLithium system

The battery and PCS sizes come from your loads above. Choose how the system connects; the single-line diagram, the container and the bill of materials update as you go.

Single-line diagram

DC current AC current (50 Hz) Control / data

Inside a GeoLithium container

Hover over or tap each part to see what it is and why it is there. A 20-foot liquid-cooled container holds about 3.7–5 MWh of LFP cells today; smaller systems use outdoor cabinets with the same parts.

Step 3

Bill of materials and estimate

Indicative 2026 prices for India, excluding GST, set by GeoSolar. The estimate rebuilds as you change the design. A final quote follows a site survey and load study.

Estimated project cost

–

ComponentQuantityRate (₹)Amount (₹)

Every component and why it is needed

A battery energy storage system is much more than batteries. These are the parts of a complete GeoLithium BESS, from the cell to the cooling and fire systems.

LFP cells

The basic storage unit. Lithium iron phosphate (LFP) prismatic cells, typically 280–314 Ah at 3.2 V (about 1 kWh each), are now standard for stationary storage.

Why it is needed: LFP is the safest lithium chemistry for large systems (high thermal-runaway temperature, no cobalt) and lasts 6,000–10,000 cycles.

Typical specification: 3.2 V nominal, 280–314 Ah, 6,000+ cycles at 80% DoD (manufacturer rated), IEC 62619 / UL 1973 certified.

Battery modules and module BMS

Groups of 16–52 cells in series in a steel or aluminium case, with a slave board that measures every cell voltage and temperature.

Why it is needed: Modules make cells safe to handle and let the BMS watch each cell, catch faults early and balance the cells.

Typical specification: 51.2 V–166 V per module, passive or active balancing, NTC temperature sensors.

Battery racks and rack BMS (BCU)

Modules stacked in series in a rack, reaching 1,000–1,500 V DC, with a rack controller, main contactors, fuse and current sensor.

Why it is needed: The rack controller can disconnect its rack on any fault, so one bad rack never takes the whole system down.

Typical specification: 1,000–1,500 V DC, pre-charge circuit, rack fuse, Hall-effect current sensor, CAN / Modbus to the system BMS.

System BMS (BAU)

The top level of the three-level battery management system, collecting data from every rack.

Why it is needed: It calculates state of charge and health, sets charge and discharge limits for the PCS and trips the system if anything goes out of range.

Typical specification: SOC / SOH estimation, insulation monitoring, alarm and trip logic, data logging.

DC combiner and DC switchgear

Brings all rack outputs onto one DC bus with fuses, a DC breaker and an isolator.

Why it is needed: Provides short-circuit protection and a safe way to isolate the battery for maintenance.

Typical specification: Rated for 1,500 V DC, DC-rated fuses and breakers, surge protection devices.

PCS (power conversion system)

A bidirectional inverter: it charges the battery from AC (rectifier) and discharges it back to AC (inverter).

Why it is needed: Batteries store DC, while the grid, DG and machines run on AC. The PCS also controls how fast power flows and, in grid-forming mode, creates a stable grid when there is no utility supply.

Typical specification: 415 V 3-phase output, 97–98.5% efficiency, 110–150% short overload, grid-following and grid-forming modes, IEC 62477-1.

Hybrid inverter

Combines a battery converter and solar MPPT chargers in one unit (DC coupling).

Why it is needed: Solar can charge the battery directly on DC without an extra conversion, saving cost and space. It suits systems up to a few hundred kW.

Typical specification: Built-in MPPTs, battery port, grid and backup ports, typically 98% peak efficiency.

Solar PV array and solar inverter

Rooftop or ground-mounted modules. In AC-coupled systems a separate string inverter feeds solar onto the AC bus.

Why it is needed: Solar charges the battery for free during the day, so the stored energy displaces grid or diesel power in the evening.

Typical specification: Tier-1 TOPCon / mono PERC modules, string inverters with MPPT, DC SPD and string fuses.

Transformer and RMU

Steps 415 V up to 11 kV (or the site voltage) and a ring main unit switches the HT connection.

Why it is needed: Needed only when the BESS connects to an HT (11 kV or higher) supply; small LT systems connect directly at 415 V.

Typical specification: Dry or oil-type, ONAN, vector group per DISCOM, with HT breaker / RMU.

LT panel and protection relays

The AC switchboard where the PCS, grid, DG and load feeders meet, with breakers and relays.

Why it is needed: Protects people and equipment from faults, and isolates the BESS from the grid during an outage (anti-islanding).

Typical specification: ACB / MCCB, over-current, earth-fault, reverse-power and under/over voltage-frequency relays.

Grid metering

A DISCOM-approved bidirectional (net) meter with CTs and PTs.

Why it is needed: Measures energy imported and exported, and is required by the DISCOM for any grid-connected storage or solar.

Typical specification: Class 0.2S / 0.5S, CT / PT set, AMR / AMI communication.

DG synchronisation panel / ATS

Lets the BESS and diesel generator run together, or transfers the load between them.

Why it is needed: The BESS can then start the DG only when the battery runs low, keep it at efficient loading and cut fuel use sharply.

Typical specification: Auto-start / stop contacts, synchroniser, load sharing, reverse-power protection.

EMS / microgrid controller

The site-level controller that decides when to charge and discharge.

Why it is needed: It runs the use cases (peak shaving, solar time-shifting, backup, DG optimisation) automatically against tariffs and limits.

Typical specification: Modbus TCP, CAN, IEC 61850, cloud dashboard, tariff schedules, export limits.

Thermal management (liquid cooling or HVAC)

A chiller pumps coolant through cold plates under the cells (liquid cooling), or air conditioners cool the container (air cooling).

Why it is needed: Cell life and safety depend on temperature. LFP lasts longest near 25 °C; liquid cooling keeps the cell-to-cell spread to about 3 °C against 5–10 °C for air cooling, which matters in Indian summers.

Typical specification: Chiller with redundant pumps, glycol-water coolant, leak detection; or precision HVAC with N+1 units.

Fire detection and suppression

Smoke, heat and off-gas (hydrogen, carbon monoxide) detectors linked to an aerosol, clean-agent or water-mist system.

Why it is needed: Off-gas detection gives the earliest warning of a failing cell; suppression stops a fire spreading. NFPA 855 requires detection and, for walk-in units, suppression.

Typical specification: Multi-level detection, fire alarm panel, aerosol / Novec 1230 / water mist, manual release and alarms.

Explosion control and ventilation

Deflagration vent panels on the roof and an exhaust fan triggered by gas detection.

Why it is needed: Gas from a failing cell can build up in a closed container; venting and exhaust keep it below explosive levels (NFPA 68 / 69).

Typical specification: Pressure-relief panels, explosion-proof exhaust fan, gas-detector interlock.

Container / enclosure

A 10 ft, 20 ft or 40 ft container, or outdoor cabinets for smaller systems.

Why it is needed: Protects the equipment from dust, rain and corrosion, holds the cooling and fire systems, and keeps people away from live parts.

Typical specification: IP54–IP55, C4 / C5 corrosion protection, insulated walls, 20 ft holds about 3.7–5 MWh of LFP today.

Auxiliary power and UPS

A small supply for the BMS, EMS, cooling, lights and fire panel, backed by a UPS.

Why it is needed: Safety systems must keep working even when the battery is disconnected or the grid fails.

Typical specification: Auxiliary transformer / DB, online UPS for controls and fire panel.

Cables, earthing and lightning protection

DC and AC power cables, cable trays, earth pits and a lightning arrester.

Why it is needed: Correctly sized cables keep losses and heat down; good earthing protects people and makes protection relays work.

Typical specification: DC-rated solar / battery cables, armoured AC cables, earth resistance typically below 1 Ω.

Monitoring, SCADA and security

Data logger, communication link, cloud dashboard, CCTV and access control.

Why it is needed: Lets the operator and GeoSolar see every rack and alarm remotely and respond fast.

Typical specification: 4G / fibre link, Modbus / IEC 61850, 1-second data, role-based access.

Civil works

RCC plinth, cable trenches, drainage, fencing and signage.

Why it is needed: A level, drained foundation and safe spacing between containers are part of fire-safety design.

Typical specification: Designed for container weight (about 35–42 t for a 20 ft 5 MWh unit), with fire-separation distances.

Safety standards a BESS should meet

  • IEC 62619: safety of lithium cells and batteries for industrial use, including stationary storage.
  • IEC 62933 series: electrical energy storage systems, covering terminology, performance testing and system safety.
  • UL 9540: safety of the complete energy storage system (battery, PCS and controls together). UL 9540A: large-scale test of how a cell thermal runaway spreads; now also required for large-scale fire testing in NFPA 855.
  • NFPA 855: installation of stationary energy storage, including spacing, detection, suppression and explosion control (with NFPA 68 / 69).
  • IEC 62477-1: safety of power electronic converters such as the PCS. IEC 61850 / Modbus: communication between BMS, PCS and EMS.
  • India: connection follows the CEA technical standards and safety regulations and your DISCOM's rules; cells and packs should carry BIS certification where it applies.

How the battery size is calculated

Energy (kWh): how long it lasts

Battery size = energy needed ÷ (usable depth of discharge × system efficiency) × ageing margin. Energy needed is each load's watts × hours (× duty cycle for fridges and ACs that switch on and off), times the days of autonomy. LFP batteries can safely use about 90% of their capacity, lead-acid only about 50%, which is why a lead-acid bank must be nearly twice as big. We allow about 90% for inverter and battery losses (about 94% for industrial PCS).

Power (kW and kVA): what it can run at once

The inverter or PCS must carry every load that runs together. Motors draw apparent power, so kVA = kW ÷ power factor, and we add 25% headroom. When a motor starts it draws a surge: about 6× for direct-on-line starters, 2.5× for star-delta, 3× for soft starters and 1.2× with a VFD. The inverter's short-term overload (about 2× for 10 seconds on home hybrid inverters, about 1.5× on industrial PCS) must cover the largest motor starting while everything else keeps running.

C-rate: can the battery deliver that power?

A battery's discharge rate limits its power: a 0.5C battery delivers half its kWh as kW, so a 200 kW load needs at least 400 kWh at 0.5C even if it only runs for an hour. The calculator takes the larger of the energy and the power requirement.

Voltage and current

Small home systems use 24 V batteries (up to about 3 kVA) and larger ones 48 V. Industrial BESS run at high DC voltage (about 600 to 1,000 V), which keeps cable currents low. Ah = Wh ÷ battery voltage.

These are planning figures. We confirm the final design after a site survey and, for industry, a load study with logged demand data. See battery energy storage systems, off-grid vs hybrid solar and the solar calculator.

Frequently asked questions

How is an industrial BESS sized?

By both energy and power. Energy is the kWh the machines use over the backup or peak period, divided by depth of discharge and efficiency, plus an ageing margin. Power is the running kW plus the starting surge of the largest motor, which sets the PCS rating, and the battery's C-rate must be able to deliver that power.

Can a BESS start heavy motors and compressors?

Yes, if the PCS is sized for the starting kVA. Direct-on-line motors draw about 6 times their running current, star-delta about 2.5 times and VFD drives only about 1.2 times, so soft starters or VFDs on large machines make the BESS smaller and cheaper.

What is a BESS calculator?

A tool that estimates the battery energy (kWh) and power conversion system rating (kW/kVA) a battery energy storage system needs, from the machines it must run, how long, their power factor and how they start.

What C-rate should an industrial BESS use?

Most commercial and industrial LFP systems are 0.5C, meaning they deliver their full energy over about two hours. Short, heavy loads such as backup for large motors may need 1C, while long-duration storage uses 0.25C. The battery must be big enough to deliver the peak kW at its C-rate, even if the energy needed is small.

How big is a BESS container?

Small systems up to about 100 kWh fit in wall or rack cabinets; outdoor cabinets hold about 200 to 260 kWh each; a 20-foot container typically holds about 3.5 to 5 MWh of LFP batteries with cooling and fire protection.

Can a BESS replace a diesel generator?

For outages of a few hours, yes. A BESS switches over in milliseconds, has no fuel cost or emissions, and can also cut peak demand charges and store solar on the days the grid is fine. For very long outages it is often paired with a smaller DG set.

What are the main components of a BESS?

LFP cells grouped into modules and racks; a three-level battery management system (BMS); DC combiner and switchgear; a power conversion system (PCS) or hybrid inverter; AC switchgear, metering and, for HT connections, a transformer; an energy management system (EMS); liquid cooling or HVAC; fire detection, suppression and explosion venting; the container; auxiliary power; cables, earthing and civil works.

What is the difference between a PCS and a hybrid inverter?

A PCS is a bidirectional inverter that only converts between the battery (DC) and the AC bus; solar then needs its own string inverter (AC coupling). A hybrid inverter adds solar MPPT chargers to the same unit, so solar can charge the battery directly on DC (DC coupling). Hybrid inverters suit systems up to a few hundred kW; larger and retrofit projects usually use a separate PCS.

Should I choose AC-coupled or DC-coupled storage?

AC coupling is easiest when solar or DG sets are already installed, and scales well because the battery and solar are independent. DC coupling avoids one conversion step, so slightly more solar energy reaches the battery, and it can capture solar that an AC-limited inverter would otherwise clip. New solar-plus-storage projects often use DC coupling; retrofits usually use AC coupling.

What does the BMS do, and why are there three levels?

The module BMS measures every cell voltage and temperature, the rack BMS (BCU) controls each rack's contactors and fuse, and the system BMS (BAU) calculates state of charge and health and tells the PCS how much power it may use. Splitting it this way lets a single faulty rack be disconnected without shutting the whole system down.

What does the EMS do?

The energy management system is the site controller. It decides when to charge and discharge based on tariffs, solar output, demand limits and backup needs, and starts or stops the DG set in a microgrid.

Why do BESS containers use liquid cooling?

Cell life and safety depend on temperature. Liquid cooling keeps cells near 25 °C with a cell-to-cell spread of about 3 °C, against roughly 5–10 °C for air cooling, which allows denser containers and works better in hot Indian summers.

How is a BESS protected against fire?

In layers: cell-level monitoring by the BMS; smoke, heat and off-gas (hydrogen and carbon monoxide) detection for the earliest warning; aerosol, clean-agent or water-mist suppression; deflagration vents and exhaust fans to stop gas building up; and safe spacing between containers. NFPA 855 and UL 9540A testing set out how these are designed and proven.

What is the round-trip efficiency of a BESS?

The share of energy you get back after charging and discharging. Large containerised systems quote about 90–94% including conversion and cooling (Tesla, for example, lists 93.7% for a 4-hour Megapack 2 XL), while smaller commercial systems typically achieve 85–90% once auxiliary loads are included.

How long does a BESS last?

LFP cells are rated for about 6,000–10,000 cycles. Running one cycle a day, that is typically 10–15 years, and warranties usually guarantee around 60–70% of the original capacity at the end of the term. An ageing margin in the sizing keeps the system meeting its duty in later years.

How much does a BESS cost in India?

Published 2026 figures put utility-scale installed cost at roughly ₹13,000–18,000 per kWh, commercial and industrial systems of 2 MWh and above at about ₹15,000–25,000 per kWh, and smaller 100–500 kWh systems at about ₹25,000–40,000 per kWh. The bill of materials on this page shows how the cost builds up for your design.

Do I need a transformer for a BESS?

Only if the system connects to an HT supply (11 kV or above). Most commercial and small industrial systems connect at 415 V through the LT panel; larger sites with their own HT substation add a step-up transformer and RMU.

Can a BESS work without the grid?

Yes. In off-grid or outage conditions the PCS runs in grid-forming mode and creates the 415 V, 50 Hz supply itself, with solar and a DG set charging the battery. The PCS must be rated for grid-forming operation and for the starting surge of your largest motors.

What approvals does a BESS need in India?

Typically the DISCOM's connection approval (and net or bidirectional metering where energy is exported), inspection by the electrical inspectorate (CEIG) before energisation, and compliance with local fire-safety requirements. GeoSolar handles these as part of the project.